A flow meter measures flow. A flow transmitter turns that measurement into a signal that the rest of your plant can use: a PLC that controls a dosing pump, a SCADA system that trends flow across a site, a batch controller that stops a fill at the right volume, or a data logger that records water use for reporting.
Choosing the right output is one of the most important and most often overlooked parts of specifying a flow meter. Get it right and the meter drops straight into your system. Get it wrong and you are left with extra converters, rewiring or a meter that cannot talk to the equipment it was bought for. This guide explains the main output types in plain English: 4–20 mA, pulse, HART and Modbus, as well as industrial Ethernet and wireless. It also covers when to use each one and what to check before you order.
Flow Meter vs Flow Transmitter: A Quick Refresher
The sensor is the part of the meter that sits in or on the pipe and detects the flow. The transmitter is the electronics that processes the sensor’s signal, displays the reading and produces the outputs. On some meters the transmitter is built into the same housing. On others it is mounted separately and connected by cable. For a full explanation, see our guide to what a flow transmitter is and how it differs from a flow meter.
The Main Output Types at a Glance
| Output | What it sends | Best for |
|---|---|---|
| 4–20 mA | Flow rate as a current | Control loops, trending, simple integration |
| Pulse / frequency | Pulses per unit volume, or frequency proportional to flow | Totalising, batching, billing |
| Relay / status | On/off signals | Alarms, flow direction, limit switching |
| HART | Digital data on top of 4–20 mA | Diagnostics and configuration over existing wiring |
| Modbus RS485 | Digital data over a serial network | Multiple instruments on one cable, data loggers |
| Industrial Ethernet | Digital data over Ethernet | Plants built on PROFINET or EtherNet/IP |
| Wireless / cellular | Data sent remotely | Remote sites without cabling |
4–20 mA Analogue Output
The 4–20 mA current loop has been the standard for industrial instrumentation for decades, and it is still the most widely used output on flow transmitters.
How it works
The transmitter sets a current between 4 mA and 20 mA in proportion to the flow rate. At the bottom of the configured range, typically zero flow, it sends 4 mA. At the top of the range it sends 20 mA. Anything in between is a straight-line proportion. For example, if a meter is ranged 0 to 100 L/min, a flow of 50 L/min produces 12 mA.
Why 4 and not 0?
The 4 mA starting point is known as a live zero. If the signal drops to near 0 mA, the control system knows there is a fault, such as a broken wire or failed transmitter, rather than simply no flow. Many transmitters also drive the signal to a defined level outside the normal range when they detect an internal fault, so the control system can raise an alarm.
Why it is still so popular
- Current signals are resistant to electrical noise and do not lose accuracy over long cable runs the way voltage signals can.
- Almost every PLC, SCADA input card, controller and panel meter accepts 4–20 mA.
- It is simple to test and troubleshoot with a standard multimeter.
What to watch for
- Scaling. The range set in the transmitter must match the range set in the control system. A mismatch is one of the most common causes of readings that look plausible but are wrong.
- Loop power. Some outputs are active, meaning the transmitter powers the loop. Others are passive, meaning the PLC input card or a separate supply powers it. Confirm which your transmitter and input card expect before wiring.
- Totals. A 4–20 mA signal represents flow rate, not total volume. Totalising it in a PLC is possible but less accurate than using a pulse output.
Pulse and Frequency Outputs
Pulse outputs send a burst of pulses, with each pulse representing a fixed volume of liquid. Frequency outputs send a pulse train whose frequency rises and falls with the flow rate.
When to use a pulse output
- Totalising. Counting pulses gives an accurate running total, which is why pulse outputs are standard for water use reporting and billing.
- Batching. Batch controllers count pulses and stop the fill when the target volume is reached.
- Connecting to remote displays and data loggers. Many low-power devices accept pulse inputs directly.
Scaled pulses and K-factors
A raw pulse output from a sensor, such as the pulses from an oval gear or turbine meter, has a K-factor: the number of pulses per litre. A scaled pulse output has already been converted so that each pulse equals a convenient unit, such as one pulse per litre or per 10 litres. Scaled pulses make configuration in the receiving device simpler.
What to watch for
- Pulse rate limits. Make sure the receiving device can count pulses as fast as the meter produces them at maximum flow.
- Output type. Common types include open collector, voltage pulse and reed switch. The receiving input must match.
- Direction. Quadrature pulse outputs use two channels to indicate flow direction and help reject false counts, which is useful where flow can reverse.
Rate totalisers such as the Flomec RT40 accept pulse inputs from a meter, display rate and total locally, and can re-transmit a scaled pulse or a 4–20 mA signal when externally powered, making them a simple way to add outputs to a basic pulse meter.
Relay and Status Outputs
Relay or status outputs switch on and off in response to a condition. Common uses include high and low flow alarms, empty pipe alarms, flow direction indication and fault alarms. They are simple, but very useful for protecting pumps and alerting operators without needing any programming in the control system. For simple on/off flow detection without measurement, a dedicated flow switch may be all you need.
HART: Digital Data Over Analogue Wiring
HART (Highway Addressable Remote Transducer) overlays a digital signal on top of a standard 4–20 mA loop. The analogue signal carries on working exactly as before, while a HART-capable system or handheld communicator can read extra information over the same two wires, including:
- Totals and secondary measurements
- Diagnostic and alarm information
- Configuration settings, which can be changed remotely
HART is a good choice when you want richer data and remote configuration but need to keep existing 4–20 mA wiring and input cards.
Modbus RS485
Modbus is a straightforward, widely supported digital protocol. Over an RS485 connection, several instruments can share one cable, each with its own address. A PLC, data logger or SCADA system acting as the master reads values such as flow rate, totals and alarm status from each device in turn.
- Advantages: fewer cables, access to many values from one device, and support in most PLCs, loggers and SCADA packages.
- What to check: baud rate, addressing, register map and cable termination. Your system integrator will need the transmitter’s Modbus register documentation.
Industrial Ethernet: PROFINET and EtherNet/IP
Larger plants increasingly run their control systems on industrial Ethernet. PROFINET is common on Siemens-based systems, while EtherNet/IP is common on Rockwell-based systems. A transmitter with a native Ethernet interface connects directly to the plant network, providing fast access to all its data without separate analogue wiring.
The best protocol is usually whichever one your plant already uses. Adding a single device on a different protocol means extra gateways and configuration.
Wireless and Remote Communication
At remote sites such as bores, reservoirs and network pits, running cable is often impractical. Some meters include cellular modems or connect to telemetry units that send readings back to a central system. The battery-powered SITRANS F M MAG 8000, for example, offers an optional built-in wireless module for remote data access, so readings can be collected without visiting the site.
A Modern Example: Modular Outputs
Newer transmitters increasingly offer outputs as plug-in modules, so the same transmitter can be configured for different systems. The Siemens SITRANS FMT020 flow transmitter, the current-generation transmitter for Siemens electromagnetic flow meters, offers communication modules including HART, Modbus RS485, PROFINET and EtherNet/IP, along with SD card data logging and a large graphical display. Paired with a sensor such as the SITRANS FMS500, it forms a complete electromagnetic flow measurement system that fits into most control architectures. Browse our full range of electromagnetic flow meters for more options.
Wiring, Power and Signal Basics
- Power supply. Confirm whether the transmitter needs mains power, low-voltage DC, loop power or battery power, and what is available at the installation point.
- Cable type. Use shielded, twisted-pair cable for analogue and serial signals, earthing the shield at one end only unless the manufacturer specifies otherwise.
- Separation. Run signal cables away from power cables and variable speed drives to reduce interference.
- Isolation. Galvanically isolated outputs prevent ground loops between the transmitter and the control system.
- Hazardous areas. Where flammable vapours or dust may be present, outputs and wiring must meet the relevant hazardous area requirements.
Pre-Purchase Checklist: Specifying Outputs Correctly
- What will receive the signal: a PLC, SCADA, data logger, batch controller or panel meter?
- What inputs does that device have: analogue, pulse, serial or Ethernet?
- Do you need flow rate, total volume or both?
- Which protocol does your control system already use?
- Do you need alarms, such as high flow, low flow or empty pipe?
- Can flow reverse, and do you need to measure it in both directions?
- What power is available at the meter?
- How far is the meter from the receiving device?
- Is the site hazardous or remote?
Answering these questions before ordering avoids the most common integration problems. If you are still deciding on the meter technology itself, our flow meter selection guide is a good place to start.
Need Help Matching Outputs to Your System?
BES Flowmeters has supplied flow meters, transmitters and process control instrumentation to Australian industry since 1986. We can help you specify a meter that connects directly to your existing equipment.
Not sure which meter suits your application? Call BES Flowmeters on (03) 5956 8685 or email sales@besflowmeters.com.au and our team will help you match the right meter to your pipe, fluid and budget.
Frequently Asked Questions
What is the most common output on a flow transmitter?
The 4-20 mA analogue output is the most common. It represents the flow rate as a current between 4 mA (zero or the bottom of the range) and 20 mA (the top of the range), and is accepted by almost every PLC, SCADA system, controller and panel meter.
Why does a 4-20 mA signal start at 4 mA instead of 0?
Starting at 4 mA creates a live zero. A reading of 4 mA means zero flow, while a reading near 0 mA means something is wrong, such as a broken wire or a failed transmitter. This lets the control system tell the difference between no flow and a fault.
What is the difference between a pulse output and a 4-20 mA output?
A 4-20 mA output represents the instantaneous flow rate, which suits control and trending. A pulse output sends one pulse for a set volume of liquid, which suits totalising, batching and billing, because counting pulses gives an accurate total volume.
What does HART add to a 4-20 mA output?
HART adds a digital signal on top of the standard 4-20 mA loop without disturbing it. The control system still reads the analogue flow signal, while a HART-capable system or handheld can read extra data such as totals, diagnostics and configuration over the same two wires.
Should I choose Modbus or an industrial Ethernet protocol?
Modbus RS485 is simple, widely supported and works well for connecting several instruments to a PLC or data logger. Industrial Ethernet protocols such as PROFINET and EtherNet/IP suit larger plants already built around those networks. The right choice is usually whichever protocol your existing control system already uses.